three phase input single phase output ups system 10kva

Prostar SP10K three phase input single phase output ups system 10kva

Three Phase in Single Phase out UPS | 10KVA/8KW | 192Vdc | Pure Sine Wave Output

SKU: SP10K Category:

Prostar SP10K three phase input single phase output ups system 10kva promises efficient and economical operation with a flexible power system. Matching ancillary cabinets provide the ability to meet specific demands for run time, bypass and parallel requirements.

Prostar SP10K three phase input single phase output ups system 10kva is a three-phase, double-conversion online UPS that provides a complete power protection solution. In a footprint that is up to 75 percent smaller than comparable UPSs, an integrated power distribution module and a maintenance bypass switch.

Three phase input single phase output ups has been designed as combined advanced IGBT technology with hi-frequency wider-modulated technology (PWM), which make customer could obtain hi-quality power output and optimized efficiency under each operation load.

Prostar three phase in single phase out UPS is possible to parallel up to 2 units UPS to build out redundancy or add capacity with less space than a typical large UPS requires.

three phase in single phase out ups

UPS System 10KVA Features

1. Intelligent control of multiple CPU

Groups of new microprocessor (CPU) co-ordination,which can precisely control the parameters of UPS and its full control,providing sufficient computing power, to ensure UPS always in top working condition.

2. Humanized display interface

LCD dot matrix display,which visually indicated the UPS’s operating parameters.LED displays the working status of UPS,and the LCD + LED combinations could make you get the UPS running status clearly and quickly.

3. High-intelligence network control

Through the communication interface,with the monitoring software,which can directly monitor UPS on the computer,simplified power management;optional adapter remote monitor (SNMP card),with a variety of operating system and application software,as well as TCP / IP , SNMP,HTTP and other protocol support,which meets the users′requirements to monitor UPS via network, this is more suitable for decentralized users to centralized manage,thereby achieving the real global Management. Offers multiple audible and visual alarms to immediately alert you to an input voltage fluctuation (buck/boost), output overload, low battery or replace battery condition.

4. Not principal and subordinate type, but adaptive parallel technology

It has strong ability in parallel and does not need to set the quantity of parallel, it can be arbitrary online parallel expansion or N + 1 redundancy in parallel. Parallel UPS will share the same group batteries.

5. Intelligent battery management

Adopts a three-stage charging method, which is good for recovery for the deep discharge of the battery.Independent current sharing and parallel charger, which can increase he capacity according to request.It can guarantee the charging request for the long backup UPS system.With the battery reverse connect protection, short circuit protection and over temperature protection, and other functions.

UPS Details

three phase in single phase out ups front n rear

UPS System 10KVA Schematic

three phase in single phase out ups connection

UPS Parallel Connection

three phase in single phase out ups parallel connection

Ideally Suited for

  • Industrial Automatic Control
  • Medical Equipment
  • Office Automation
  • Light Industrial Applications
  • Production Equipment
  • Electronic & Telecom
  • Bank ATM
  • Aeronautics & Astronautics
  • Army Technology
  • Securities System

The Articles You may Like

    Request Product Price

    10KVA Online UPS Specifications

    Model SP10K
    Capacity 10KVA/8KW
    Noise 48dB~54dB(Distance 1 Meter)
    Dimension(WxDxH mm) 343x624x1020
    Weight(Kgs) 139
    INPUT
    Voltage 380Vac/400Vac/4150Vac ± 25%
    Frequency 50Hz/60Hz±10%
    Power Factor ≥0.91
    OUTPUT
    Voltage 220Vac/230Vac/240Vac ± 1%
    Frequency 50Hz/60Hz±0.05%
    Harmonic Distortion Linear load<3%, Non-linear load<5%
    Overload Capacity 110%≥300Min, 125%≥10Min, 150%≥1Min
    Crest Factor 3:1
    Wave Form Pure sine wave
    Transfer Time 0ms
    BATTERY
    Type Support VRLA Battery
    D.C. Voltage 192Vdc
    Max. Charging Current 0.2AxC10
    Charging Time(Standard) 12hours
    SYSTEM
    Protection Input over-voltage, under-voltage; output overload, shortcircuit; Inverter over-temperature; Battery under-voltage,over-voltage
    IP Protection IP20
    Parallel Mode N+1 can be in parallel with differenct power capacity
    Software Interface Windows9x,2000,NT,ME,XP,Linux,Novell,Macosx,NT4.0
    Meantime Between Failures 300,000Hours
    ENVIRONMENT
    Operating Temperature 0℃ to 40℃
    Humidity 0~95% (non-condensing)
    Altitude <1000m (with increase of 100m,it will reduce output of 1%) max. 4000m
    Storage Temperature -15℃ to 50℃
    MANAGEMENT
    Communication Interface RS232
    SNMP Power managemetn from SNMP manager and web browser