High Frequency Online UPS | 10KVA/9000W | 192Vdc | 208V/220V/230V/240V | Without battery inside | Single phase
Prostar PHT1110-PRO best single phase online computer power supply ups 10kva also has USB and RS-232 communication ports as standard, with a built-in intelligent slot for additional adapters, protocol converters and relate contact cards.
Computer ups 10kva is a single phase on line UPS with pioneering technology that provides output power factor up to unity and high AC-AC efficiency. With easy installation, the compact uninterruptible power supply, this UPS will assure device protection and provide several minutes runtime in case of main power failure.
PHT1110-PRO best single phase online computer power supply ups 10kva is double-conversion high frequency online UPS with a output power factor 0.9. Specifically designed for operation in poor power areas. It is suited for all critical business usages such as networks, data centers, banking and building automation. Users also can adjust charging current from 1A to 6A according to different applications.
To avoid damage and protect your equipments and IT network, install an Uninterruptible Power Supply system like UPS 10kva as it is the safest approach to ensure high quality electrical supply.
Fig 1. Uninterruptible power supply front panel
Fig 2. Uninterruptible power supply rear
MODEL | PHT1110-PRO | |
CAPACITY | 10KVA / 9000W | |
Battery Voltage | 192V | |
Size, D X W X H (mm) | 442 X 190 X 318 | |
Net Weight (kgs) | 12 | |
INPUT | ||
Norminal Voltage | 208/220/230/240VAC | |
Input Voltage Range | 110-300VAC (Based on load @50%) 176-300VAC (Based on load @100%) |
|
Frequency Range | 46Hz ~ 54Hz or 56Hz ~ 64Hz | |
Phase | Single Phase | |
Power Factor | ≧ 0.99 @ nominal voltage (input voltage) | |
OUTPUT | ||
Output voltage | 208/220/230/240VAC | |
AC Voltage Regulation | ± 1% (Batt. Mode) | |
Frequency Range(Synchronized Range) | 46Hz ~ 54Hz @ 50Hz or 56Hz ~ 64Hz @ 60Hz | |
Frequency Range (Batt. Mode) | 50 Hz or 60Hz ± 0.1% | |
Overload | 105%~110%: UPS shuts down after 10 min at battery mode or transfer to bypass when the utility is normal 110%~130%: UPS shuts down after 1min at battery mode or transfer to bypass when the utility is normal >130%:UPS shuts down after 3seconds at battery mode or transfer to bypass when the utility is normal |
|
Current Crest Ratio | 3:1 | |
Harmonic Distortion | ≦ 3 % THD (Linear Load);≦ 5% THD (Non-linear Load) | |
Transfer Time | AC Mode to Batt. Mode | 0 ms |
Inverter to Bypass | 0 ms | |
Waveform (Batt. Mode) | Pure Sine Wave | |
EFFICIENCY | ||
AC Mode | 93% | |
Battery Mode | 91% | |
BATTERY | ||
Battery Type | Depending on applications | |
Battery Numbers | 16 – 20 (adjustable) | |
Recharge Time | Depending on applications | |
Charging Current | 1.0A/2.0A/4.0A/6.0A (6A is only available for 16Pcs batteries) | |
Charging Voltage | 218.4/273VDC ± 1% | |
ENVIRONMENT | ||
Operation Humidity | 20-90 % RH @ 0- 40°C (non-condensing) | |
Noise Level | Less than 50dBA @ 1 Meter | |
MANAGEMENT | ||
Smart RS-232 or USB | Windows® 2000/2003/XP/Vista/2008、Windows® 7/8、Linux、Unix、MAC | |
Optional SNMP | Power management from SNMP manager and web browser |