Prostar PHT1106-PRO 1 phase multi-functional online ups 6kva

High Frequency Online UPS | 6KVA/5400W | 192Vdc | 208V/220V/230V/240V | Without battery inside | Single phase

SKU: PHT1106-PRO Category:

Prostar PHT1106-PRO single phase double conversion security camera ups 6kva also has USB and RS-232 communication ports as standard, with a built-in intelligent slot for additional adapters, protocol converters and relate contact cards.

Security camera ups 6kva is double-conversion high frequency online UPS with a output power factor 0.9. Specifically designed for operation in poor power areas. Users can adjust charging current from 1A to 6A according to different applications. It is also suitable for all critical business usages such as networks, data centers, banking and building automation. 

double conversion security camera ups 1kva

PHT1106-PRO single phase double conversion security camera ups 6kva is designed to eliminate disturbances to workstations, POSs, ATMs or home appliances. For longer backup time requirements you can add an external battery pack to enhance availability for critical applications. Using on-line, double-conversion technology, this UPS protects equipment from the full range of power disturbances, including sags, surges and noise, without drawing on battery power, extending battery life and minimizing replacements.

UPS 6kva Benefits

  • VFI topology (online / double conversion) protection against all mains network problems
  • Output power factor 0.9
  • Microprocessor control optimizes reliablility
  • Input power factor correction
  • Wide frequency input range (40-70 Hz Auto Sensing) allows for Generator power to be used as a primary or secondary input power source
  • Extremely wide input voltage window of 110 VAC to 300 VAC
  • ECO and frequency operating voltage possibilities
  • Expansion slot for SNMP, potential free contacts, remote display
  • Graphic LCD display with interactive multilingual user interface
  • Internal hardware data logger with plain text display and date / time stamp
  • Emergency power off (EPO) on terminal block
  • Provides early-warning fault analysis ensuring proactive component replacement

Computer UPS Structures

double conversion security camera ups 1kva front

Fig 1. Uninterruptible power supply front panel

 

Fig 2. Uninterruptible power supply rear

 

The Articles You may Like

MODEL PHT1106-PRO
CAPACITY 6000VA / 5400W
Battery Voltage 192V
Size, D X W X H (mm) 369 X 190 X 318
Net Weight (kgs) 12
INPUT
Norminal Voltage 208/220/230/240VAC
Input Voltage Range 110-300VAC (Based on load @50%)
176-300VAC (Based on load @100%)
Frequency Range 46Hz ~ 54Hz or  56Hz ~ 64Hz
Phase Single Phase
Power Factor ≧ 0.99 @ nominal voltage (input voltage)
OUTPUT
Output voltage 208/220/230/240VAC
AC Voltage Regulation ± 1% (Batt. Mode)
Frequency Range(Synchronized Range) 46Hz ~ 54Hz @ 50Hz or 56Hz ~ 64Hz @ 60Hz
Frequency Range (Batt. Mode) 50 Hz or 60Hz ± 0.1%
Overload 105%~110%: UPS shuts down after 10 min at battery mode or transfer to bypass when the utility is normal
110%~130%: UPS shuts down after 1min at battery mode or transfer to bypass when the utility is normal
>130%:UPS shuts down after 3seconds at battery mode or transfer to bypass when the utility is normal
Current Crest Ratio 3:1
Harmonic Distortion ≦ 3 % THD (Linear Load);≦ 5% THD (Non-linear Load)
Transfer Time AC Mode to Batt. Mode 0 ms
Inverter to Bypass 0 ms
Waveform (Batt. Mode) Pure Sine Wave
EFFICIENCY
AC Mode 92%
Battery Mode 90%
BATTERY
Battery Type Depending on applications
Battery Numbers 16 – 20 (adjustable)
Recharge Time  Depending on applications
Charging Current 1.0A/2.0A/4.0A/6.0A (6A is only available for 16Pcs batteries)
Charging Voltage 218.4/273VDC ± 1%
ENVIRONMENT
Operation Humidity 20-90 % RH @ 0- 40°C (non-condensing)
Noise Level Less than 50dBA @ 1 Meter
MANAGEMENT
Smart RS-232 or USB Windows® 2000/2003/XP/Vista/2008、Windows® 7/8、Linux、Unix、MAC
Optional SNMP Power management from SNMP manager and web browser